Loading...
generator-parts

Auto Start Generator Control Module

Model / SKU: 5110

Available for quote Price on request

Chinese

 

Specifications

Controller Overview



     
  • Product Type: Auto Start Generator Control Module

  •  
  • Model: 5110

  •  
  • Application: Automatic start and stop control for diesel and gas generating sets with non-electronic engines

  •  
  • Display: Back-lit LCD display with front LED fault indication

  •  
  • Mounting: Front panel mounting

Key Functions



     
  • Automatic generator start and stop control

  •  
  • Engine monitoring and protection

  •  
  • Configurable inputs and outputs

  •  
  • Configurable alarms and timers

  •  
  • Front panel programming

  •  
  • PC configuration support where applicable

  •  
  • Remote monitoring support where applicable

Protection and Fault Monitoring



     
  • Under speed and over speed monitoring

  •  
  • Charge failure monitoring

  •  
  • Emergency stop monitoring

  •  
  • Low oil pressure shutdown

  •  
  • High engine temperature shutdown

  •  
  • Fail to start and fail to stop protection

  •  
  • Loss of speed sensing signal monitoring

Electrical Specifications



     
  • DC Supply: 8V to 35V continuous

  •  
  • Cranking Dropout: Survives 0V for 50ms when supply conditions are met

  •  
  • Start Relay Output: 16A DC at supply voltage

  •  
  • Fuel Relay Output: 16A DC at supply voltage

  •  
  • Auxiliary Relay Outputs: 5A DC at supply voltage

  •  
  • Charge Fail / Excitation Range: 0V to 35V

  •  
  • Maximum Operating Current: 320mA at 12V, 215mA at 24V

  •  
  • Maximum Standby Current: 175mA at 12V, 95mA at 24V

Generator and Sensor Inputs



     
  • Alternator Input Range: 15V L-N to 333V AC L-N maximum

  •  
  • Alternator Input Frequency: 50-60Hz at rated engine speed

  •  
  • Magnetic Pick-Up Voltage Input: +/- 0.5V to 70V peak

  •  
  • Magnetic Input Frequency: Up to 10,000Hz at rated engine speed

  •  
  • Analogue Inputs: Oil pressure and engine temperature sender inputs

Instrumentation Display



     
  • Generator volts: L1-N, L2-N, L3-N

  •  
  • Generator volts: L1-L2, L2-L3, L3-L1

  •  
  • Generator amps: L1, L2, L3

  •  
  • Generator frequency

  •  
  • Engine speed RPM

  •  
  • Oil pressure

  •  
  • Engine temperature

  •  
  • Plant battery voltage

  •  
  • Engine run hours

Dimensions



     
  • Module Size: 240mm x 172mm

  •  
  • Panel Cut-Out: 220mm x 160mm

  •  
  • Maximum Panel Thickness: 8mm

Note


This is a legacy/older style auto start controller. Compatibility should be confirmed against the generator wiring, sensors, supply voltage, panel cut-out and configuration requirements before installation or replacement.